Schneider Electric PKL36120U64AE1 Picture Illustration: Dimensions Drawing for P-Frame Lug-Lug (H 16.3 in.) 4 videos Circuit breaker, PowerPacT P, 1200A, 3 pole, 600VAC, 65kA, lugs, Micrologic 6.0P, 80%, modbus PKL36120U64AE1
CategoryCircuit Breaker
In Stock · Ready to Ship
Ships within 3 business days
Product Details
Specifications
| Range | PowerPact |
|---|---|
| Product name | PowerPact P |
| Product or Component Type | Circuit breaker |
| Device Application | Distribution |
| Line Rated Current | 1200 A |
|---|---|
| Number of Poles | 3P |
| Control Type | Toggle |
| Breaking capacity code | K |
| Breaking capacity | AIR 65 kA 240 V AC 50/60 Hz UL 489 AIR 50 kA 480 V AC 50/60 Hz UL 489 AIR 50 kA 600 V AC 50/60 Hz UL 489 Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2 |
| [Ue] rated operational voltage | 600 V AC 50/60 Hz UL 489 |
| Network Frequency | 50/60 Hz |
| [Ics] rated service breaking capacity | 25 kA 240 V AC 50/60 Hz IEC 60947-2 25 kA 380/415 V AC 50/60 Hz IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Trip unit technology | Electronic, power, MicroLogic 6.0 P, LSI |
| Continuous current rating | 80 % |
| [Ui] rated insulation voltage | 750 V IEC 60947-2 |
| Trip unit name | MicroLogic 6.0 P |
| Accessory / separate part type | Modbus connecting cable |
| AWG gauge | 4 x 3/0 AWG...500 kcmil aluminium/copper |
| Local signalling | Overload 1 trip indicator green) 1 trip indicator green) Trip causes 1 trip indicator green) |
| Mounting mode | Unit mount lug) |
| Mounting Support | Lug |
| Electrical connection | Lugs, line Lugs, load |
| Terminal identifier | AL1200P25K |
| Long time pick-up adjustment range | 0.4...1 x Ir |
| Tightening torque | 442.5 lbf.in (50 N.m) 0.1…0.4 in² (95…240 mm²) (4 x 3/0 AWG...500 kcmil) 8.9…11.5 lbf.in (1.0…1.3 N.m) |
| Number of slots | 2 auxiliary switch OF plug-in) 1 alarm switch SD plug-in) 1 overcurrent trip switch SDE plug-in) 1 voltage release MN or MX plug-in) |
| Power wire stripping length | 1.2 in (30 mm) |
| Height | 16.16 in (410.46 mm) |
| Width | 8.27 in (210.06 mm) |
| Depth | 8.05 in (204.47 mm) |
| Net Weight | 32 lb(US) (14.5 kg) |
| Quantity per Set | 1 |
| Communication interface | Modbus |
| Circuit breaker application | HACR rated |
| Quality labels | CE |
|---|---|
| Standards | UL CSA NEMA NOM-003-SCFI-2000 IEC 60947-2 |
| Product certifications | UL CSA NOM |
| IP degree of protection | Front cover IP40 |
| Pollution degree | 3 IEC 60947-1 |
| Ambient Air Temperature for Operation | -13…158 °F (-25…70 °C) |
| Ambient Air Temperature for Storage | -58…185 °F (-50…85 °C) |
| Operating altitude | < 6561.68 ft (2000 m) without derating 13123.36 ft (4000 m) with derating |
| GTIN | 3606486285688 |
|---|---|
| Returnability | No |
| Unit Type of Package 1 | PCE |
|---|---|
| Nbr. of units in pkg. | 1 |
| Package 1 Height | 16.1 in (41.0 cm) |
| Package 1 Width | 8.3 in (21.0 cm) |
| Package 1 Length | 8.03 in (20.4 cm) |
| Package weight(Lbs) | 32.0001 lb(US) (14.515 kg) |
| Warranty (in months) | 18 |
|---|
Specifications
| Brand | Square D |
|---|---|
| Category | Circuit Breaker |
| Shipping weight | 32.0 lb |
Need a datasheet, cross-reference, or bulk pricing? Request a quote
Shipping & Returns
-
Ships in One Business Days
In-stock orders are packed and handed to the carrier within 3 business days. Tracking is emailed as soon as it ships.
-
30 Business Day Returns
Unused items in original packaging can be returned within 30 business days of delivery.
-
LTL Delivery
Large or heavy items ship via LTL freight carrier. Lift-gate delivery is included at no extra charge.


Schneider Electric PKL36120U64AE1 Picture Illustration: Dimensions Drawing for P-Frame Lug-Lug (H 16.3 in.) 4 videos Circuit breaker, PowerPacT P, 1200A, 3 pole, 600VAC, 65kA, lugs, Micrologic 6.0P, 80%, modbus PKL36120U64AE1
$21,000.00
Customer reviews
Be the first to review this product.